Dismantling The Electronics Module; Mounting The Electronics Module - Festo CPX-F8DE-P Manual

Input module terminal cpx
Hide thumbs Also See for CPX-F8DE-P:
Table of Contents

Advertisement

2. Installation

2.3.1 Dismantling the electronics module

2.3.2 Mounting the electronics module

2-10
1. Switch off operating and load voltage supplies to the CPX
terminal.
2. Unscrew and remove mounting screws aJ è Fig. 1/1.
3. Carefully lift off connection block 1, 2 or 3.
4. If required, carefully remove electronic module 4 from
the bus bars.
Ensure prior to assembly that the PROFIsafe address on
the electronic modules is set correctly è Chapter 2.4.
Note
Handle the components with care.
Ensure that the interconnecting block is clean and free of
foreign bodies, especially on and near the contact rails.
Check the seal and the sealing surfaces. Replace dam­
aged parts.
Ensure that connecting surfaces are clean. This helps to
optimise the sealing action and to prevent contact faults.
1. Position input module correctly in interconnecting
block 6 without tilting it and press it to the stop
è Fig. 1/1.
2. Align connection block 1, 2 or 3 and fit to electronic
module 4.
3. Screw the mounting screws aJ into the existing threads.
4. Screw the mounting screws crosswise.
Tightening torque: 0.9 ... 1.1 Nm.
Festo P.BE-CPX-F8DE-P-E N en 1610a English