High threshold (humidity): If the humidity exceeds the set threshold, a notification is triggered if enabled. The
l
default value is 90%.
Low threshold (humidity): If the humidity falls below the set threshold, a notification is triggered if enabled.
l
The default value is 5%.
Hysteresis (humidity): Hysteresis must be set to prevent multiple notifications if humidity fluctuates around a
l
threshold. The default value is 5%.
The high alarm disappears when the value drops below the high threshold minus the hysteresis value.
The low alarm disappears when the value returns above the low threshold plus the hysteresis value.
Input #1 and Input #2: An identifier corresponding to the acquired contact (for example: rack door, air
l
conditioning, or generator unit). The maximum length is 28 characters.
when closed and when open: The names associated with the two contact positions (for example "open" and
l
"closed" for a door, "on" and "off" for a generator).