8 General Specifications

Mains supply (L1, L2, L3):
Supply voltage
Mains voltage low / mains drop-out:
During low mains voltage or a mains drop-out, the FC continues until the intermediate circuit voltage drops below the minimum stop level, which
corresponds typically to 15% below the FC's lowest rated supply voltage. Power-up and full torque cannot be expected at mains voltage lower than
10% below the FC's lowest rated supply voltage.
Supply frequency
Max. imbalance temporary between mains phases
True Power Factor (λ)
Displacement Power Factor (cosφ) near unity
THiD
Switching on input supply L1, L2, L3 (power-ups)
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 480/690 V maximum.
Motor output (U, V, W):
Output voltage
Output frequency
Switching on output
Ramp times
* Voltage and power dependent
Torque characteristics:
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
*Percentage relates to the frequency converter's nominal torque.
Cable lengths and cross sections:
Max. motor cable length, screened/armoured
Max. motor cable length, unscreened/unarmoured
Max. cross section to motor, mains, load sharing and brake *
Maximum cross section to control terminals, rigid wire
Maximum cross section to control terminals, flexible cable
Maximum cross section to control terminals, cable with enclosed core
Minimum cross section to control terminals
* See Mains Supply tables for more information!
Digital inputs:
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
i
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
®
MG.20.T1.02 - VLT
is a registered Danfoss trademark
8 General Specifications
380-480 V ±10%
50/60 Hz ±5%
3.0 % of rated supply voltage
> 0.98 nominal at rated load
(> 0.98)
maximum once/2 min.
overvoltage category III / pollution degree 2
0 - 100% of supply voltage
0 - 800* Hz
Unlimited
1 - 3600 sec.
maximum 110% for 1 min.
maximum 135% up to 0.5 sec.
maximum 110% for 1 min.
1.5 mm
2
/16 AWG (2 x 0.75 mm
2
1 mm
/18 AWG
2
0.5 mm
/20 AWG
0.25 mm
18, 19, 27
1)
, 29
1)
, 32, 33,
PNP or NPN
0 - 24 V DC
< 5 V DC
> 10 V DC
> 19 V DC
< 14 V DC
approx. 4 kΩ
> 5%
8
*
*
*
150 m
300 m
2
)
2
4 (6)
28 V DC
161