2 Safety

2.1.8 IT Mains

IT mains
Do not connect frequency converters with RFI-filters to mains supplies with a voltage between phase and earth of more than 440 V
for 400 Vs and 760 V for 690 V converters.
2
For 400 V IT mains and delta earth (grounded leg), mains voltage may exceed 440 V between phase and earth.
For 690 V IT mains and delta earth (grounded leg), mains voltage may exceed 760 V between phase and earth.
Par. 14-50
RFI Filter can be used to disconnect the internal RFI capacitors from the RFI filter to ground. Par. 14-50 RFI Filter on both the drive and the
filter must be turned off.