A7" Swing Flap Motor Malfunction / Lock - Daikin SkyAir Service Manual

R-410a, 50hz
Hide thumbs Also See for SkyAir:
Table of Contents

Advertisement

Troubleshooting by Remote Controller Display / LED Display
5.9

"A7" Swing Flap Motor Malfunction / Lock

A7
Remote
Controller
Display
LED indications
The table below shows the LED indications.
Operation
Normal
Malfunctioning
Error generation
The error is detected by the limit switch when the motor turns.
When ON/OFF of the microswitch for position detection cannot be reversed eventhough the
swing flap motor is energized for a specified amount of time (about 30 seconds).
Supposed
The possible causes are:
Causes
164
Failure of swing flap motor
Failure of microswitch
Failure of connector connection
Failure of indoor unit PC board
HAP (green)
5
5
SiBE28-804
HBP (green)
5
5
Troubleshooting