Replacing a Device

3.2.2 Managing Device Information

3-10
: Remember to adjust or redefine any TLPs you have designated
Note
to accumulate the information for the decommissioned device's
logical position.
If a particular wireless device in your network stops working, you can
easily replace it with a similar device.
: Using this option does not require you to adjust or redefine any
Note
TLPs you have designated to accumulate the information for the
decommissioned device's logical position. The new device
assumes all parameters you have defined for the old device.
First, configure the device for the network, assigning it the appropriate
Network ID and Join Key. Install the device in the field. Start
ROCLINK 800, select the IEC 62591 module, and display the
Commission tab. When the replacement device appears on the
Uncommissioned list, select it and drag it on top of the non-working
device. This tells ROCLINK 800 that you want this new device to
assume all the defined characteristics of the old device.
ROCLINK 800 displays a verification dialog to prevent you from
accidentally replacing a device:
Figure 3-7. Device Replacement Verification Dialog
Click Yes to complete the replacement. ROCLINK commissions the
new device and automatically decommissions the old device, moving it
to the Uncommissioned list.
Once you have commissioned a device, the Transmitter tab can provide
you with a variety of information on that device. Select the Transmitter
tab to display the Transmitter screen:
: When viewing a transmitter connected to a THUM adaptor,
Note
only the process variables are returned to the IEC62591 module.
Configuration and Commissioning
Revised June-2018