2.3.2 Wiring the IEC 62591 Module to the Field Link

2-6
Connect the positive power lead to the "+" power terminal and the
3.
negative power lead to the "–" power terminal.
Connect the data + lead to the "A (+)" terminal and the data – lead
4.
to the "B (–)" terminal (see Figure 2-4).
5.
Plug and seal any unused conduit connectors.
6.
Replace the housing cover.
B
A. Data A (+)
B. Data B (–)
C. Return
D. +10.5 to 30 Vdc
Figure 2-4. Field Link Power and Data Wiring
Since the ROC800 and FB107 modules use the same PCB, you wire the
modules to the Field Link in the same way. Figure 2-5 shows wiring for
the FB107 IEC 62591 module; Figure 2-6 shows wiring for the
ROC800 IEC 62591 module.
: The wire loop between connectors 1 and 3 and between
Note
connectors 2 and 4 provides termination for the RS-485
connections between the Field Link and the module.
Installation
C
D
Revised June-2018