IEC 62591 Wireless Interface Instruction Manual (for ROC800-Series and FloBoss 107)
Revised June-2018
Field
Messages Received
Message Nacks
Transmitted
Message Nacks
Received
Message Retries
Received
Session Initiates
Received
Session Restarts
Transmitted
Set Time Messages
Transmitted
Set Time Messages
Received
Reset APM Messages
Transmitted
Reset APM Messages
Received
Tunnel Messages
Transmitted
Configuration and Commissioning
Description
This read-only field shows the number of
messages IEC62591 module has received from the
Field Link.
This read-only field shows the number of NACKs
the IEC62591 module has sent to the Field Link. A
NACK is typically sent when a received message
contains an error and a retransmission request is
sent. A high number of NACKs is often an
indication of a poor link connection.
Reserved
This read-only field shows the number of retry
requests the IEC62591 module has received from
the Field Link. A retry request is sent by the Field
Link when it does not receive an acknowledgement
from the IEC62591 module. A High number of
retries is often an indication of a poor link
connection.
This read-only field shows the number of Session
Initiates the IEC62591 module has received from
the Field Link. A Session Initiate is sent by the Field
Link when it wants to start and/or restart
communications with the IEC62591 module (for
example, after the Field Link (first powers up).
This read-only field shows the number of Session
Restart requests the IEC62591 module has sent to
the Field Link. A Session Restart request is sent by
the IEC62591 module to request a bus restart of
the communications with the Field Link (for
example, after the IEC62591 module first powers
up).
This read-only field shows the number of Set Time
messages the IEC62591 module has sent to the
Field Link. A Set Time message is part of the time
management process used to keep the
WirelessHART network time up to date.
This read-only field shows the number of Set Time
messages the IEC62591 module has received from
the Field Link.
This read-only field shows the number of Reset
APM messages the IEC62591 module has sent to
the Field Link. A Reset APM message is part of the
wireless management process used to restart the
WirelessHART radio on the Field Link.
This read-only field shows the number of Reset
APM messages the IEC62591 module has received
from the Field Link.
This read-only field shows the number of Tunnel
messages the IEC62591 module has sent to the
Field Link. A Tunnel message is part of the wireless
management process used to send information
across the WirelessHART network.