IEC 62591 Wireless Interface Instruction Manual (for ROC800-Series and FloBoss 107)
3-34
Field
HART Command
Execution Status
Events
Configuration and Commissioning
Description
This read-only field shows an indicator when the
IEC 62591 module sends a HART command to the
sensor, and that command is unsuccessful. Each bit
of the indicator represents the following HART
command:
Bit 0
Command 103 Message 0
Bit 1
Command 103 Message 1
Bit 2
Command 104 Message 0
Bit 3
Command 104 Message 1
Bit 4
Command 107 Message 0
Bit 5
Command 107 Message 1
Bit 6
Command 108 Message 0
Bit 7
Command 108 Message 1
Bit 8
Command 109 Message 0
Bit 9
Command 109 Message 1
Bit 10
Command 117
Bit 11
Command 118
Bit 12
Spare
Bit 13
Spare
Bit 14
Spare
Bit 15
Spare
Note: This field shows the status of important
commands for Bursting and Events.
▪ Bursting
o Command 103 Write Burst Period – Writes Min
and Max burst update periods
o Command 104 Write Burst Triggers – Sets
burst trigger mode
o Command 107 Write Burst Device Variables -
Burst device variables returned by device on
command 9 or 33 in burst mode
o Command 108 Write Burst mode command
number
o Command 109 Burst Mode Control – Sets
bursting ON/OFF
▪ Event Notification
o Command 117 Write Event notification timing
– Sets Event notification retry time, Maximum
update time, Event De-bounce interval
o Command 118 Event notification control -
Enable/ Disable event notification
Displays the Publish Time, Max Publish Time,
Debounce Interval, Cur Event Time, Event
Summary, Control Code and Events Pending
Revised June-2018