IEC 62591 Wireless Interface Instruction Manual (for ROC800-Series and FloBoss 107)
Caution
Revised June-2018
Tab
Integrity
Uninstall
Commission
To begin to commission the network, select the Network tab. The
Network screen displays:
Configure all devices belonging to a site to use the same Network ID
and Join Key. To avoid network errors, configure all devices in
adjacent networks to us a different Network ID and Join Key.
Configuration and Commissioning
Description
Displays any integrity problems with the wireless
network.
Note:
If a transmitter has a problem, this field
turns red and displays a message
identifying the transmitter at fault (here, the
transmitter in logical position 2).
Click to uninstall the IEC 62591 module and restore
factory defaults. Since the FB107 automatically
recognizes installed modules, it immediately
redisplays the module in the graphic interface.
Note:
Click this button to reset all values for the
module back to factory default. You must
redefine all values for your network.
Click to access the Commission screen, which
displays all devices the Field Link has identified for
the network.
Figure 3-3. Network screen