IEC 62591 Wireless Interface Instruction Manual (ROC800-Series and FloBoss 107)
Caution
FB107 To install a module in the FB107:
Caution
2-2
▪ If a module is currently in the slot, unscrew the captive screws
and remove that module. Store it in an anti-static bag.
▪ If the slot is currently empty, remove and store the module
cover.
Insert the module through the module slot in the front of the
4.
ROC800 or EXP housing. Make sure that the label on the front of
the module faces right side up (see Figure 1-2). Gently slide the
module in place until it contacts properly with the connectors on the
backplane.
: If the module stops and does not go any farther, do not force
Note
the module. Remove the module and see if the pins are bent.
If the pins are bent, gently straighten the pints and re-insert
the module. The back of the module must connect fully with
the connectors on the backplane.
Tighten the captive screws on the front of the module.
5.
Wire the module to the Field Link (refer to Wiring the Modules and
6.
Field Link section in this chapter).
Replace the wire channel cover.
7.
Never connect the sheath surrounding shielded wiring to a signal
ground terminal or to the common terminal of an I/O module. Doing so
makes the module susceptible to static discharge, which can
permanently damage the module. Connect the shielded wiring sheath
only to a suitable earth ground.
If any processes require backup, arrange for that before removing
power from the device.
1.
Remove power from the device.
2.
Perform one of the following:
▪ If a module is currently in the desired slot, remove the module
and store it in an anti-static bag.
▪ If the slot is currently empty, remove and store the module
cover.
: When you install an IEC 62591 module in the FB107's slot
Note
2, the firmware redirects the COM2 communications port on
the CPU to the module installed in slot 2. To prevent this
from occurring, install the module in slot 3 through slot 7.
Close the module cover (the piece with ridged edges) against the
3.
body of the module. This enables the locking mechanism to secure
the module in the slot.
Installation