3-6
: The values initially shown in the Network ID and Join Key
Note
fields in Figure 3-3 are default values. You must change these
to your network-specific ID and join keys and save the
configuration to flash memory. This prevents the default values
from overwriting your network-specific values during a cold
start.
Complete the Network ID and Join Key fields with the Network ID and
Join Key you have defined for the transmitters.
Field
Network ID
Join Key (hex)
Status
Enable Active
Advertising
Click Apply. As the Field Link processes your request to add the device
to the network, the value displayed in the Status field changes:
▪ Initializing. The module is in the boot-up sequence. The module
sends info (Part Number, firmware version, etc.) to the RTU. During
this time, the module is not yet communicating with the RTU. Once
the code starts up (usually after 30-60 seconds), the module switches
from Initializing to Configuring Network.
Configuration and Commissioning
Description
Enter a five-character Network ID. Valid values are
1 to 36863.
Should be noted that each IEC62591 Module / RTU
can only have a single Network ID. The "grouping"
should be related to the control/monitoring network
for a given RTU.
For example if two RTUs are installed at a site,
each grouping should be the set of meter runs each
RTU controls.
Note: A Network ID cannot be all zeros (such as
00000).
Enter a valid Join Key to permit the device to
access its defined network.
A Join Key is a 128-byte value expressed as four
32-bit portions. As shown in the example, you can
use zeros for the first three parts of the Join Key.
This read-only field shows the current status of the
connection between the network and ROCLINK
800.
Click to enable active advertising, in which the IEC
62591 module continuously broadcasts network
information. This enables new devices to quickly
join the network. Active advertising broadcasts
network information continuously for approximately
30 minutes.
Additionally, active advertising occurs automatically
when:
You first power up or restart the IEC 62591
module; or
A device leaves the network (which allows
communications to re-establish).