IEC 62591 Wireless Interface Instruction Manual (for ROC800-Series and FloBoss 107)
3-12
Field
Transmitter
Information
Comm Status This read-only field shows the status of the
Device Status This read-only field shows the Field Device Status
Commission Status This read-only field shows the current status of the
Poll Mode
Process Variables on
Reset
Configuration and Commissioning
Description
This section displays read-only information reported
by the transmitter, including serial number,
manufacturer ID, type of device, battery life, and
other data.
Note: Battery life is calculated by the transmitter.
Refer to the transmitter's manufacturer for
further details.
communications channel.
code to indicate the current communication and
operating state of the transmitter. For any value
other than 0, the field turns red.
Note: Hover your mouse over this field to view the
meaning of the response code. Response
codes are manufacturer-defined. Refer to the
documentation provided with the transmitter
or to the manufacturer's website for a
complete list of response codes, their
meanings, and their resolutions.
device in the commissioning process. Valid values
are:
0 = Idle (not used)
1 = Configuring Burst Command
2 = Configuring Burst Variables
3 = Configuring Burst Rate
4 = Enabling Bursting
5 = Bursting (field highlighted in green)
6 = Data Stale (field highlighted in yellow)
7 = Communication Failure (field highlighted in red)
8 = Disabling Bursting
Indicates the mode the transmitter uses to acquire
information. The default is Normal, based on the
value in the Burst Rate field. Select Update and click
Apply to immediately perform an on-demand polling
and refresh all fields on this screen. The mode
reverts to Normal at the next Burst Rate interval.
Sets the process variables to use after a failure.
Valid values are Retain Last Value (use the last
known values for the process variables) or Use
Failsafe Value (use the values entered in the PV
Failsafe, SV Failsafe, TV Failsafe, and QV Failsafe
fields).