IEC 62591 Wireless Interface Instruction Manual (for ROC800-Series and FloBoss 107)
Revised June-2018
▪ Configuring Network. The code is running and the module is
attempting to pull configuration info from the RTU. If the
Initializing status is taking too long, it means that either
▪ the board is not completely booting up, or
▪ the application code is not correctly loading. As a result, the
sequence cannot complete.
▪ Detecting radio. The Field Link recognizes the network.
▪ On-Line. When the Status field shows On-line, you can begin
commissioning devices for the network.
Select the General tab, and click Commission. The IEC 62591 Module
screen displays.
Figure 3-4. IEC 62591Module
The screen has four tabs:
Tab
Commission
Transmitter
Statistics
Diagnostics
Configuration and Commissioning
Description
Auto-detects available uncommissioned devices
and enables you to add them to the defined
network.
Accesses both read-only statistics and modifiable
parameters for a specific device associated with the
network.
Note:
You must first commission a device before
you can access this tab.
Provides read-only statistics the Field Link has
accumulated for the network. Click Reset
Statistics to reset these values at any time.
Describes how to use the module's USB port to
generate log information for resolving issues.