IEC 62591 Wireless Interface Instruction Manual (for ROC800-Series and FloBoss 107)
Caution

2.2 Installing the Field Link

2.2.1 Optimizing the Location

Revised June-2018
Insert the module in the slot on the base unit or expansion rack,
4.
making sure that the module faces the correct direction (see Figure
1-2). Gently slide the module into place until it contacts properly
with the connectors on the backplane.
: If the module stops and does not go any farther, do not force
Note
the module. Remove the module and see if the pins are bent.
If the pins are bent, gently straighten the pints and re-insert
the module. The back of the module must connect fully with
the connectors on the backplane.
5.
Wire the module to the Field Link (refer to Wiring the Modules and
Field Link section in this chapter).
Never connect the sheath surrounding shielded wiring to a signal
ground terminal or to the common terminal of an I/O module. Doing so
makes the module susceptible to static discharge, which can
permanently damage the module. Connect the shielded wiring sheath
only to a suitable earth ground.
Proceed to Installing the Field Link.
6.
This section covers where and how to install the Field Link.
Mount the Field Link in a location that provides convenient access to
the host system network (wireless I/O devices) and the network of
wireless field devices. Find a location where the Field Link has optimal
wireless performance. Ideally, this is 4.6 to 7.6 m (15-25 ft) above the
ground or 2 m (6 ft) above obstructions or major infrastructures. See
Figure 2-1.
Figure 2-1. Mounting the Field Link
Installation
2-3