Figure 3-8. Transmitter screen
:
Notes
▪ You can also double-click a commissioned device on the
Commission screen to immediately access the Transmitter screen for
that device.
▪ If you use ROCLINK to change transmitter values when the
transmitter is busy with other communications tasks, the transmitter
may fail to update and reverts to previous values. If this occurs, you
can use ROCLINK to re-attempt the update when the transmitter is
not busy with other communications tasks. Alternately, avoid this
issue entirely by using a 475 Field Communicator to change
transmitter values.
Field
Transmitter
Tag
Message
Descriptor
Configuration Change
Counter
Configuration and Commissioning
Description
Displays the 40-character alphanumeric tag
associated with the transmitter. The system adds the
logical position (here, 2 -) to the tag. Click  to
display all devices currently defined for this network.
Defines a 40-character alphanumeric identifier for
the transmitter (such as Tank2Level or
Pump1NorthTemporary).
Provides an optional 40-character message
associated with the transmitter. Use this field for
explanatory or warning messages (such as Not to
exceed 300 psi).
Provides an optional 20-character alphanumeric
descriptor for the transmitter (such as Casing press).
This read-only field shows the number of times the
configuration of the transmitter has been changed,
as reported by the transmitter itself.