IEC 62591 Wireless Interface Instruction Manual (for ROC800-Series and FloBoss 107)
2.2.4 Grounding the Field Link
2.3 Wiring the Module and Field Link
2.3.1 Wiring the Field Link
Revised June-2018
Figure 2-3. Field Link Mounting
For further information on grounding the field link, refer to the
documentation that accompanied the device (Emerson™ Wireless 781
Field Link Quick Installation Guide, part 00825-0100-4421)
This section assumes you have already successfully installed the IEC
62591 module in either a ROC800 or a FB107 and installed the Field
Link in its permanent field location.
Communications between the IEC 62591 module and the Field Link
occur through an RS-485 connection. Remote Automation Solutions
recommends that you use shielded, twisted-pair cable for I/O signal
wiring. The twisted-pair minimizes signal errors caused by electro-
magnetic interference (EMI), Radio Frequency Interference (RFI), and
transients. The removable terminal blocks on the module accept wire
sizes 16 to 22 AWG.
: Ensure that wiring between the ROC800 or FB107 IEC 62591
Note
module and the Field Link meets all appropriate local
requirements (use of conduit, etc.).
1.
Power down the IEC 62591 module (if it is currently powered).
Remove the housing cover identified on the casing as "Field
2.
Terminals."
Installation
2-5