ABB i-bus KNX Product Manual page 96

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Enable coded status emergency test
Options:
This parameter enables the 1 byte communication object Emergency test trigger/status. This com-
munication object indicates a fault of the emergency lighting converter on the KNX.
With the option yes, two further parameters appear:
94 2CDC 507 114 D0201 | DGN/S 1.16.1
yes
no
yes: The communication object Emergency test trigger/status is enabled. The communication
object sends a coded telegram, which triggers an emergency lighting test and sends its status
on the KNX. The coding can be taken from the description of the communication object
Emergency test
status, page 115.
no: No emergency lighting test is triggered by the DGN/S using an individual communication
object.
send object value
Options:
after a change
after request
after a change or request
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change or a request.