ABB i-bus KNX Product Manual page 119

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
34
This communication object is enabled if in
set with the option yes.
Telegram value:
35
This communication object is enabled if in
set with the option yes.
The information indicating that an emergency lighting situation is present is sent on the KNX via this communication object. If
this is the case in
criterion must be parameterized.
Emergency lighting operation is triggered in the DGN/S via this object by a telegram with the value 1. In
Gx
Group, page 51, the parameter Enable with function slave emergency determines whether the lighting group goes to slave
emergency lighting operation.
Telegram value
36
This communication object is enabled, if in
nication object: "Start autom. emergency test" 1 Bit has been parameterized with yes. This communication relates exclusively
to all emergency lighting converters.
The start request of the automatic emergency lighting test is passed on from the DGN/S to the emergency lighting converter
via this communication object. The start itself is triggered by the emergency lighting converter (e.g. battery must be loaded). In
Parameter window - Cx...Cy
An emergency lighting test that is automatically triggered can be a functional test or duration test. The automatic emergency
lighting test must be supported by emergency lighting converters (device type 1 to EN 62386-202). This is only an optional
requirement according to the standard.
In order to avoid that not all emergency lighting is performing an emergency lighting test or a recharging cycle, in
window Emergency
The formula used for the offset is the formula DALI short address multiplied with the offset. Converter 1 has an offset of 15
minutes, converter 2 has an offset of 30 minutes etc., if a delay of 1 (= 15 minutes) is parameterized.
Telegram value
The DGN/S passes on this time just as the actual emergency lighting trigger signal to the emergency lighting converter. If and
which of the timing tolerances the conditions actually start, depends on the state of the emergency lighting converter and its
timing tolerances. The emergency lighting converter can, for example, be in the recharging cycle (20 hours is not uncommon)
and the (pending) test does not start.
37...39
Communication objects are not used
Function
Emergency test stop
Parameter window -
1 = all emergency lighting tests are stopped.
0 = no function
Slave emergency active/status
Parameter window -
Parameter window -
Emergency, page 39, under the parameter Pass slave emergency / Slave emergency
1 = activate slave emergency lighting
0 = deactivate slave emergency lighting
Autom. emergency test start
Parameter window Emergency
Test, page 95, the emergency lighting test should be parameterized as automatic.
Converter, page 90, an offset for two neighbouring emergency lighting converters can be parameterized.
1 = start automatic emergency lighting test
0 = stop automatic emergency lighting test
Empty
Communication object name
DALI output
Emergency, page 39, the parameter Emergency test status is
DALI output
Emergency, page 39, the parameter Pass slave emergency is
Converter 1...64
Converter, page 90, the parameter Enable commu-
DGN/S 1.16.1 | 2CDC 507 114 D0201 117
Data type
Flags
1 bit
C, W, T
DPT 1.010
1 bit
C, R, W, T
DPT 1.010
Parameter window
1 bit
C, W, T
DPT 1.010
Parameter