ABB i-bus KNX Product Manual page 45

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Status response of switching state
of the DALI output
Options:
no: The status of the switch state is not actively sent on the KNX.
yes: via object "Switch/status": The common communication object Switch/status (no. 10) receives the
switch telegram, and the current status becomes active and is sent on the KNX.
yes: via separate object "Status switch": An additional communication object Status switch (no. 11) is
enabled. Using it a 1 bit telegram with the actual switch status is sent on the KNX.
Note
This status message relates to all lighting groups of the DALI output.
With a change of the parameterization or after a subsequent switching of the status object, the assign-
ment of the group addresses already allocated to the Switch communication object is lost and needs to
be reprogrammed.
If the communication object Switch/status is used for switching and status feedback, particular care
must be taken with the send properties of the communication objects.
For further information see:
With the option yes:... two further parameters appear:
no
yes: via object "Switch/status"
yes: via separate object "Status switch"
Common communication object for control telegram and
send object value
Options:
after a change
after request
after a change or request
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change or a request.
status, page 103
DGN/S 1.16.1 | 2CDC 507 114 D0201 43