ABB i-bus KNX Product Manual page 125

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
168
This communication object is enabled if in
emergency test is set with the option yes. The communication object replaces the communication object Emergency test
trigger.
An emergency lighting test can be triggered via this communication object for the emergency lighting converter x. At the same
time, the result of the emergency lighting test can be sent on the KNX or requested via this communication object.
The test result is sent on the KNX with the following coding.
The following numbering applies for the following list:
7
2
2
The bit number is identical with the exponent of the bit, e.g. number 2 complies with 2
Bit 0 ... 2
Bit 3 and 4
Bit 5
Bit 6
Bit 7
If a new test is requested on the communication object, before the ongoing test has ended, this is immediately interrupted, and
the new test is required. This is also the case when the ongoing test is requested again.
Bit 6 and 7 only relate to an emergency lighting converter. Should the DALI devices only be related to normal DALI devices, bit
6 and 7 will not be evaluated. For normal lamps and ballast faults, the communication object Fault group no. 45 and the
communication object addressed fault message no. 20 are available.
1)
The numbers of the communication objects apply for lighting groups 1...64.
Function
Emergency test trigger/status
6
5
4
3
2
1
0
2
2
2
2
2
2
= 000, stops the tests currently in operation
= 001 result relates to the functional test
= 010 result relates to the partial duration test
= 011 result relates to the duration test
= 100 result relates to the battery request
= 101 and 110 without function or the evaluation of the request is not considered
= 111 It is no valid test status available or the DALI member do not support DALI emergency converter
according IEC 6286-202. The content of Bits 3 to 7 are invalid..
= 00, testing has ended positively
= 01, testing pending, not yet started
= 10, test runs
= 11, test interrupted
= 1, testing manually started
= 1, lamp fault (converter)
= 1, device (converter) fault
Communication object name
Converter x
Parameter window Cx...Cy
Converter, page 92, the parameter Enable coded status
Data type
Flags
1 byte
C, R, W, T
non DPT
2
.
DGN/S 1.16.1 | 2CDC 507 114 D0201 123