ABB i-bus KNX Product Manual page 118

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
33
This communication object is enabled if in
object "Emergency test result" 4 Byte is parameterized with the option yes.
This communication object consists of 4 bytes. The individual bytes contain information about a DALI emergency lighting
converter. If a normal DALI device is queried, Bit 15 will get the value 1. The other Bits are invalid.
The sending behaviour using this communication object can be parameterized in the Emergency parameter window.
The following numbering applies for the following list:
High byte
31
2
2
15
2
2
The bit number is identical with the exponent of the bit, e.g. number 2 complies with 2
Bit 0...5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13...14
Bit 15
Bit 16...23
Bit 16
Bit 17
Bit 18
Bit 19
Bit 20
Bit 21
Bit 22
Bit 23
Bit 24...31
116 2CDC 507 114 D0201 | DGN/S 1.16.1
Function
Emergency test result
30
29
28
27
26
25
24
2
2
2
2
2
2
14
13
12
11
10
9
8
2
2
2
2
2
2
= contains the binary number (0...63). This number corresponds to 1 added, to the number of the DALI
device to which the information in the high byte is related
= 0 determines status value relates to an individual device (converter).
= 1, status value request. If a telegram with a set bit 7 is received, it is interpreted as a request for
diverse status messages of the DALI device, and a corresponding feedback is sent. When the answer is
sent, the value of bit 7 is set to 0
= 1, last test was function test
= 1, last test was partial duration test
= 1, last test was duration test
= 1, if one fault is detected in Bit 16... Bit 23, or battery request is not available.
= 1, battery request ended (must supported by converter, it is only an optional feature in DALI standard)
= 0, without function
= 1 It is no valid test status available or the DALI member do not support DALI emergency converter
according IEC 6286-202. The content of all other Bits are invalid.
equal DALI command 252 (query failure status)
= 1, circuit failure, converter has not reported during the test run or converter fault is detected.
= 1, battery duration fault (battery was fully discharged before the rated operating time was completed)
= 1, battery fault (no voltage or battery voltage too low)
= 1, emergency lamp fault
= 1, functional test was triggered but could not be started in the predefined time
= 1, duration test was triggered but could not be started in the predefined time
= 1, functional test fault, not passed
= 1, duration test fault, not passed
= depending on the test that has been undertaken, this highest byte contains the charge state of the
battery (0...255 = 0...100%) or the duration of the test until the battery was discharged. The value cor-
responds to the time in 2 x min
Communication object name
DALI output
Parameter window -
Emergency, page 39, the parameter Enable communication
Low byte
23
22
21
20
19
2
2
2
2
2
2
7
6
5
4
3
2
2
2
2
2
2
Data type
4 byte
non DPT
18
17
16
2
2
2
1
0
2
2
2
.
Flags
C, R, T