ABB i-bus
KNX
Commissioning
If function sequence is active (running):
Behaviour on ...
Function sequence after gateway supply
voltage recovery
Options:
This parameter defines if function Sequence is active or inactive after gateway supply voltage recovery.
After a Gateway supply voltage recovery, the parameterized brightness value in the
Gx
Fault, page 64 is set. The function Sequence is then undertaken with the option defined here.
inactive: The function Sequence is not reactivated after gateway operating voltage recovery.
active: The function Sequence is reactivated after gateway operating voltage recovery. The lighting
group is started with the next ON telegram.
last status: The function Sequence receives the operating state, which it had before gateway operat-
ing voltage failure.
Brightness value
Options:
no reaction
set function in standby
With activated function Sequence, the parameter can be used to define the reaction to a brightness
value telegram.
no reaction: A brightness value telegram is ignored.
set function in standby: A brightness telegram ends function Sequence, and the DGN/S carries
out the brightness telegram via the communication object Brightness value. The function Se-
quence is latent and waits (standby) until a renewed activation via the communication object
Activate function Sequence or via an ON telegram to the communication object Switch.
Relative dimming
Options:
no reaction
set function in standby
With activated function Sequence, the parameter can be used to define the reaction to a dimming
telegram on the communication object Relative dimming.
no reaction: A dimming telegram is ignored.
set function in standby: A dimming telegram ends the function Sequence, and the DGN/S car-
ries out the dimming telegram. The function Sequence is latent and waits until a renewed acti-
vation via the communication object Activate function Sequence or via an ON telegram to the
communication object Switch.
Recall scene
Options:
no reaction
set function in standby
With activated function Sequence the parameter can be used to define the reaction to a scene re-
call.
no reaction: A scene recall is ignored.
set function in standby: A scene telegram ends function Sequence, and the DGN/S carries out
the scene recall. The function Sequence is latent and waits until a renewed activation via the
communication object Activate function Sequence or via an ON telegram to the communication
object Switch.
inactive
active
last status
Parameter window –
DGN/S 1.16.1 | 2CDC 507 114 D0201 75