ABB i-bus KNX Product Manual page 61

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Enable with function Burn-in
(Object "Burn-in lamps/status")
Options:
This parameter defines whether the lighting group should be considered with function Burn-in. Lighting
equipment, e.g. incandescent bulbs, which does not require a burn-in phase can be excluded from the
burn-in process. They can always be dimmed independently of the function Burn-in.
The function Burn-in applies for all lighting groups even with the corresponding burn-in time and is enabled
in
Parameter window
yes: The lighting group is considered during active function Burn-in and during the burn-in phase and
it can only be switched off with 0 % brightness (OFF) and on with 100 % brightness (ON).
no: The lighting group is not taken into consideration during an activated function Burn-in and can also
be dimmed during an activated function burn-in.
Enable with slave emergency (Object
"Slave emergency active/status")
Options:
This parameter defines whether the lighting group should be considered when function Slave emergency
is activated. Hereby the functional lamps can be put into the emergency lighting state. The response of the
functional lamps during slave emergency lighting operation can be parameterized in
Emergency, page 39.
yes
no
Central, page 32.
yes
no
Parameter window -
DGN/S 1.16.1 | 2CDC 507 114 D0201 59

Advertisement

Table of Contents
loading

Table of Contents