As an example, extracts of the parameter windows for scene 1 (red) and 6 (magenta) are shown:
With scene 6 (magenta), note that the brightness value of group 7 (blue) was already at 100 % and due to
parameterization no change (no member in this Scene) has been retained.
A sequence is controlled via the communication objects Switch or Switch/status of the associated lighting
groups. The ON telegram must be sent to each lighting group involved in the sequence. In our example,
the KNX group 1/0/0 is used.
Due to the individual control it is possible to extract a lighting group from the sequence operation. In this
case, the sequence continues with the remaining lighting groups. Should just one lighting group receive an
ON telegram, only this lighting group will commence with the sequence. The other lamp groups involved
will remain unchanged.
A prerequisite for the start of a sequence is the activated function Sequence. After a download of the ap-
plication, the function Sequence is parameterized in the state, which it has after KNX voltage recovery.
144 2CDC 507 114 D0201 | DGN/S 1.16.1