ABB i-bus
KNX
Commissioning
Enable communication object
"Emergency test result" 4 Byte
Options:
no: The result of the emergency test is not actively sent on the KNX.
yes: The additional communication object Emergency test result (no. 33) is enabled. The example he-
re is of a 4 byte communication object. The low byte contains the address of an emergency lighting
converter. The three following high bytes indicate the result of the emergency lighting test. A further
parameter appears:
Pass slave emergency
Options:
The DGN/S can pass on the information about slave emergency lighting operation via the KNX or inter-
nally via the gateway to other equipment, which is in normal operation, and that can thus assume a pa-
rameterizable emergency lighting state (slave emergency). Slave emergency lighting can be triggered by
certain criteria that can be parameterized in the following.
no: Information concerning the slave emergency lighting is not passed on.
yes: The information concerning slave emergency lighting is passed on by the DGN/S. The path for
passing on information must be parameterized.
external via communication object
"Slave emergency active/status"
Options:
40 2CDC 507 114 D0201 | DGN/S 1.16.1
yes
no
Send object value
Options:
after a change
after request
after a change or request
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change or a request.
yes
no
internal to the total channel
Options:
yes
no
yes: The information concerning emergency lighting operation is passed on internally in the ga-
teway on the DALI output. No communication object is required.
no: The information concerning emergency lighting operation is not passed on internally in the
gateway on the DALI output.
yes
no
no: The information concerning slave emergency lighting is not sent externally on the KNX.
yes: The 1 bit communication object Slave emergency active/status is enabled. This communi-
cation object sends the information on the KNX indicating that emergency lighting operation
has been detected. A further parameter appears: