ABB i-bus KNX Product Manual page 95

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Prolong time after ending
fct. emergency in min [0...127]
Options:
This parameter determines the duration in minutes, which the emergency lighting lights with the brightness
value in emergency lighting operation.
Enable emergency test
Options:
This parameter enables the emergency lighting tests by the emergency lighting converter and the respec-
tive parameter window C1 Test.
yes: The parameter window C1 Test is enabled. Using the DGN/S, the tests for the emergency lighting
with the emergency lighting converter to EN 62 386-202 are determined. Two further parameters ap-
pear:
no: No tests for the emergency lighting with emergency lighting converter are carried out.
1...6...128
yes
no
Time period in which emergency test
must be started, in days [0...255]
Options:
1...7...255
It can occur that a requested emergency lighting test cannot be undertaken immediately by the
emergency lighting converter, e.g. because the emergency lighting battery is discharged. This pa-
rameter determines how long the test telegram should remain active. If a test cannot be started, a
message is issued. Parameterization is undertaken in days.
Note
Undertaking of the emergency lighting test cannot be guaranteed. The start of the test is a
reserved indicator that the test should be started as quickly as possible from the converter. If this
is not possible for technical reasons, the request remains active. The test starts at the next
possible time. The corresponding state is detected by communication object Emergency test
trigger/status (no. 169).
DGN/S 1.16.1 | 2CDC 507 114 D0201 93