Commissioning
If function Slave is active (running):
Behaviour on ...
Dimming time changeable via
obj. "Flexible time" 2 byte
Options:
yes
no
The time received via the communication object Flexible time defines the duration until the bright-
ness value received by the communication object Brightness value of slave, has been achieved.
The flexible dimming time has a value between 0...65,535 seconds.
yes: The time received via the central communication object (DALI output) Flexible time is used
as a dimming time for the switch on/off value.
no: The dimming time for the switching on and off value cannot be changed via KNX.
Switch on
Options:
no reaction
set function in standby
With activated function Slave, the parameter can be used to define the reaction to an ON telegram
on the communication object Switch or Switch/status.
no reaction: An ON telegram is ignored.
set function in standby: An ON telegram ends function Slave, and the DGN/S carries out the
switch telegram. The function Slave is latent and waits until a renewed activation (standby sta-
te) via the communication object function Activate function Slave or via a telegram with the va-
lue 1 to the communication object Switch or Switch/status.
Note
The reaction to an OFF telegram on the communication object Switch or Switch/status cannot be
parameterized. An OFF command always interrupts the function Slave. The function Slave goes
over to standby mode, in which the brightness values on the communication object Brightness
value of slave is ignored.
The function Slave is reactivated, if an ON telegram is received on the communication object
Switch or Switch/status or a telegram with the value 1 is received on communication object
Activate function Slave.
The master/slave unit is separated, for example, by deactivation of the function Slave (telegram
with the value 0 to communication object Activate function Slave). If the function Slave is not
active, the brightness values received from the function Slave via the communication object
Brightness value of slave are not available on its output.
DGN/S 1.16.1 | 2CDC 507 114 D0201 71