ABB i-bus KNX Product Manual page 59

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Dim period to reach set brightness value
("Brightness value") in s [0...65,535]
Options:
This parameter determines the time duration, in which the DGN/S sets the received brightness value for
the lighting group via communication objects Brightness value or Brightness value/status.
Dimming speed, time for 0...100 %
(Function „Relative dimming") in s [65,535]
Options:
This parameter defines the period, in which a dimming process occurs, from 0...100 %. This dimming time
only affects dimming actions, which were initiated by the communication object Relative dimming.
0...2...65,535
Dimming time changeable via
obj. "Flexible time" 2 Byte
Options:
yes
no
The time received via the communication object Flexible time has an effect on the communication
object Set brightness value. The flexible dimming time has a value between 0...65,535 seconds.
For further information see
communication object no.
yes: The time received via the central communication object Flexible time (DALI output) is used
as a dimming time until the brightness value is achieved.
no: The dimming time until the brightness value is achieved cannot be changed via the KNX.
0...5...65535
Dimming time changeable via
obj. "Flexible time" 2 Byte
Options:
yes
no
The time received via the communication object Flexible time has an effect on the dimming speed
with relative dimming. The flexible dimming time has a value between 0...65,535 seconds.
For further information see
communication object no.
yes: The time received via the central communication object (DALI output) Flexible time is used
as a dimming time for Relative dimming.
no: The dimming time for Relative dimming cannot be changed via the KNX.
27, page 112.
27, page 112.
DGN/S 1.16.1 | 2CDC 507 114 D0201 57