ABB i-bus KNX Product Manual page 88

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Example
Lighting group 1, which is dimmed from 10 % to 100 %, and lighting group 2, which is dimmed from 90
% to 100 %, achieve the parameterized brightness value of the scene simultaneously.
jump to: When a scene is recalled, the lighting groups are switched on immediately with the param-
eterized brightness value of the scene.
0.7 s...90 s: When a scene is recalled, all lighting groups of the scene are dimmed from their current
brightness value to the parameterised brightness value within this time duration.
Overwrite scene on download
Options:
yes: The scene values and the scene transition times in the DALI devices of the lighting group are
overwritten after a download or after KNX voltage recovery by the values set in the ETS.
no: The scene values and the scene transition times in the DALI devices of the lighting group are not
overwritten after a download or after KNX voltage recovery by the values set in the ETS. If no scene
values have been stored, they are parameterized by the DGN/S to the maximum brightness.
Note
With a recall scene or with a store scene, only the lighting groups, which are constituents of the
scene, are taken into consideration.
Group x brightness value of scene (x = 1...16)
Options:
Note
The options 100 % (255)...0 % (OFF) are only visible if the parameter Overwrite scene on download is
set to yes. With the option no, the possible settings are reduced to no change (no member in this scene)
and member in this scene.
This parameter defines the brightness value that is set in the lighting group when a scene is recalled.
no change (no member in this scene): This lighting group does not belong in this scene. During a sce-
ne recall, the lighting group is not influenced. The current brightness value of the lighting group re-
mains unchanged and even when the scene is stored via the KNX, the brightness value of this group
is not stored.
100 % (255)...0 % (OFF): The lighting group belongs to the scene. During a scene recall, the lighting
group is set to the parameterized brightness value here. If the set brightness value is above or below
the set maximum or minimum brightness value of the respective lighting group (see
dow Gx
86 2CDC 507 114 D0201 | DGN/S 1.16.1
yes
no
no change (no member in this scene)
100 % (255)
...
0 % (OFF)
Group, page 51), the respective brightness value is saved in the scene.