ABB i-bus KNX Product Manual page 52

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
"Fault group/device" 1 byte
enable encoded fault message
Options:
This parameter enables the communication object Fault group/device. The fault status (lamp, bal-
last fault and emergency lighting converter) of the lighting groups or the individual DALI devices are
sent on the KNX. Furthermore, the communication objects Number of faults (no. 22) and Switch up
next fault alarm (no. 24) are enabled.
For further information see:
(no.
50 2CDC 507 114 D0201 | DGN/S 1.16.1
yes
no
Communiation object no. 22 to
20), page 151
no: The communication object Fault group/device (no. 23) with the partner communication ob-
jects no. 22 and no. 24 is not enabled.
yes: The communication object Fault group/device (no. 23) with the partner communication ob-
jects (no. 22 and no. 24) is enabled. A further parameter appears:
Code correspond to group or
device
Options:
based on DALI device
group orientated
This parameter determines whether the coded fault relates to a lighting group or an individ-
ual DALI device.
based on DALI device: The value of the communication object Fault group/device re-
lates to the fault on a DALI device.
group orientated: The value of the communication object Fault group/device relates to
the fault on a lighting group.
24, page 110 and
Code table Fault group/device