ABB i-bus KNX Product Manual page 109

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
18
This communication object is enabled if in the
with the option yes.
Using this communication object, a ballast fault can be sent or read.
Telegram value
A ballast fault can occur in one of the following situations:
The ballast malfunctions and does not send telegrams on the DALI control line.
The ballast has no ballast operating voltage and does not send telegrams on the DALI control line.
The DALI control line to the ballast is interrupted, so that the DGN/S does not receive a ballast status response.
The ballast has lost its address, a query from the DGN/S remains unanswered.
Note
In order to guarantee correct evaluation of a ballast fault, the DGN/S has to know how many ballasts are to be
monitored. This is implemented by one-time activation of the communication object Detect ballasts (no. 28). Using
this function, the DGN/S independently determines which ballasts (DALI devices / DALI addresses) are connected
and uses this state as a reference value. Here not only the number but also the address of the DALI device is
registered. If this system has to be modified, the option Detect ballasts should be activated.
The process does not need to be repeated when exchanging a DALI device with the same address. The new DALI
device receives the old DALI address and assumes the position of the DALI device it replaced.
The function Detect ballasts can be triggered not only via the communication object Detect ballasts but also manu-
ally by pressing the button
Software-Tool via button Detect ballasts in the window Options.
19
This communication object is enabled if in the
with the option yes.
Using this communication object, a DALI fault can be sent or read.
There is a DALI fault if the short circuit persists for more than 500 ms.
Telegram value:
Function
Fault ballast
Parameter window -
1 = ballast fault (at least one connected ballast has a fault)
0 = no ballast fault
for more than five seconds. Furthermore, this function can be triggered with the DALI-
Fault DALI
Parameter window -
1 = DALI fault of the DALI communication
0 = no DALI fault
Communication object name
DALI output
Status, page 42, the parameter "Fault ballast" 1 Bit is set
DALI output
Status, page 42, the parameter "Fault DALI" 1 Bit is set
DGN/S 1.16.1 | 2CDC 507 114 D0201 107
Data type
Flags
1 bit
C, R, T
DPT 1.005
1 bit
C, R, T
DPT 1.005