ABB i-bus
KNX
Commissioning
Status response of lamp/ballast fault
Options:
This parameter defines how the current status of a lamp/ballast fault is sent. The communication object
Fault lamp or ballast is enabled.
yes: A status message is sent.
no: No status message is sent.
With the option yes, two further parameters appear:
send object value
Options:
Content of communication object
Options:
This parameter determines the equipment fault, which is provided on the enabled communication
object.
62 2CDC 507 114 D0201 | DGN/S 1.16.1
yes
no
after a change
after request
after a change or request
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change or a request.
Fault lamp
Fault ballast
Fault lamp or ballast
Fault lamp: The communication object Fault lamp is enabled. Using this communication object,
it is possible to provide information on whether the lighting group of a lamp has failed on the
KNX. Should there be a fault, the communication object Fault lamp is written with a 1 and sent
on the KNX in dependence on the parameterization set beforehand.
Fault ballast: The communication object Fault ballast is enabled. Using this communication ob-
ject, it is possible to provide information on whether the lighting group of a ballast has failed on
the KNX. Should there be a fault, the communication object Fault lamp is written with a 1 and
sent on the KNX in dependence on the parameterization set beforehand.
Fault lamp or ballast The communication object Fault lamp or ballast is enabled. Using this
communication object, it is possible to provide information on the KNX relating to a lamp failure
or a ballast failure in the lighting group.
Note
In order to correctly detect a ballast fault, the function Detect ballasts must however be activated
in the DGN/S. Using this function, the DGN/S notes the exact quantity of DALI devices currently
connected to the DGN/S as a reference value. Should the detected number of DALI devices
diverge from the current reference value, this will be evaluated as a ballast fault and displayed
via the communication object, in dependence on the set send parameterization on the KNX.
The function Detect ballasts can be triggered either via the communication object Detect bal-
lasts, by a long button push on the button
or by using the separate DALI-Software-Tool.