ABB i-bus KNX Product Manual page 74

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Brightness value
Options:
With activated function Slave, the parameter can be used to define the reaction to a brightness va-
lue telegram.
Relative dimming
Options:
With activated function Slave, the parameter can be used to define the reaction to dimming tele-
gram to the communication object Relative dimming.
Recall scene
Options:
With activated function Slave, the parameter can be used to define the reaction to a scene recall.
Function slave after
gateway supply voltage recovery
Options:
This parameter defines if function Slave is active or inactive after gateway supply voltage recovery.
After a Gateway supply voltage recovery, the parameterized brightness value in the
Gx
Fault, page 64, is set. The function Slave is then undertaken with the option defined here.
inactive: The function Slave is not reactivated after gateway operating voltage recovery.
active: The function Slave is reactivated after gateway operating voltage recovery. The lighting group
is controlled with the next brightness value which is received via the communication object Brightness
value of slave.
last status: The function Slave receives the operating state, which it had before Gateway operating
voltage failure.
72 2CDC 507 114 D0201 | DGN/S 1.16.1
no reaction
set function in standby
no reaction: A brightness value telegram is ignored.
set function in standby: A brightness telegram ends function Slave, and the DGN/S carries out
the brightness telegram via the communication object Brightness value. The function Slave is
latent and waits until a renewed activation via the communication object Activate function Slave
or via an ON telegram to the communication object Switch.
no reaction
set function in standby
no reaction: A dimming telegram is ignored.
set function in standby: A dimming telegram ends function Slave, and the DGN/S carries out
the dimming telegram. The function Slave is latent and waits until a renewed activation via the
communication object Activate function Slave or via an ON telegram to the communication ob-
ject Switch.
no reaction
set function in standby
no reaction: A scene recall is ignored.
set function in standby: A scene telegram ends function Slave, and the DGN/S carries out the
scene recall. The function Slave is latent and waits until a renewed activation via the communi-
cation object Activate function Slave or via an ON telegram to the communication object
Switch.
inactive
active
last status