Scan to add Modbus RTU Power Meters

Perform "Scan" to automatically build a list of Modbus RTU power
meters that are connected to the PMC/PMD. The steps are as below:
i Before performing the scan of the power meters, please make sure
the RS-485 wirings connecting to the PMC/PMD and the power
meters function well, and make sure the settings of the addresses of
the power meters are completed.
ii Click
connected to the PMC/PMD.
iii When the Scan page appears (Figure 7-4), input the starting address
and the ending address of the Modbus address that are going to
perform scan. Click on "Scan", the system will start to scan the
power meters that match the settings previously set, to cancel the
scan, click on "Cancel".
iv When the system is performing the scan (Figure 7-5), the address
that are performing scan will be dynamically shown on the upper
left side, please wait till the scan operation is completed. To stop the
scan operation, click on "Cancel" to terminal the scan and leave the
page.
to start the scan of Modbus RTU power meters that are
The "Scan" button to search Power Meter
Figure7-3 :
Figure7-4 :
Set up the Scanning Range for the Power Meters