Appendix II:Reset to Factory Default Setting and Send Password to
Administrator
During the operation of PMC/PMD, if the hardware system setting data is lost or
encounters any abnormal problem that you would like to reset the system to factory
default, please switch the Rotary Switch to specific positions to restore factory
settings or to ask PMC/PMD to send the login password to the Email account of the
Administrator. In addition, you can switch the Rotary Switch to the specific position
to delete the data logger files and reset the accumulated values of the power meter
which connect to PMC/PMD. The following figure shows the location of the Rotary
Switch of the PMC-5151.
The function of the position of the Rotary Switch:
Please follow the steps below to restore network settings to factory default or send the
login password to the Email account of the Administrator:
 Restore network settings to factory default
1. Power off the PMC/PMD.
2. Switch the Rotary Switch to position 7.
3. Power on the PMC/PMD, when the RUN/PWR LED Indicator turns to be
Rotary Switch
7
Restore network settings to factory default.
 Send the login password to the Email
8
 Delete the data logger files and reset the
Function
account of the Administrator.
accumulated values of the power meter.
Rotary Switch
297