Reference Manual
00809-0100-4026, Rev HA
H.2.2
Alarm priority
Alarms are grouped into five levels of priority:
Priority
number
0
1
2
3-7
8-15
Resource Block
Priority description
The alarm condition is not used.
An alarm condition with a priority of 1 is recognized by the
system, but is not reported to the operator.
An alarm condition with a priority of 2 is reported to the
operator.
Alarm conditions of priority 3 to 7 are advisory alarms of
increasing priority.
Alarm conditions of priority 8 to 15 are critical alarms of
increasing priority.
Appendix H: Resource block
November 2014
281