Set Transmitter Alarm; Electrical Considerations - Emerson Rosemount 3051P Reference Manual

In-line pressure transmitter with hart protocol
Hide thumbs Also See for Rosemount 3051P:
Table of Contents

Advertisement

Reference Manual
00809-0700-4001
Configure local operator interface (LOI) password using LOI
Figure 4-3: LOI Password
4.5

Set transmitter alarm

On the electronics board is an alarm switch; see
steps below to change the alarm switch location.
Procedure
1. Set loop to manual and remove power.
2. Remove transmitter housing cover.
3. Use a small screwdriver to slide switch to desired position.
4. Replace transmitter cover.
4.6

Electrical considerations

WARNING
Make sure all electrical installation is in accordance with national and local code
requirements.
Do not run signal wiring in conduit or open trays with power wiring or near heavy
electrical equipment.
Rosemount 3051P
WARNING
Cover must be fully engaged to comply with explosion proof requirements.
Electrical installation
Figure 4-2
for switch location. Follow the
April 2020
55