4.4 

Set transmitter alarm

There is an Alarm switch on the electronics board.
To change the Alarm switch location:
Procedure
1. Set loop to Manual and remove power.
2. Remove transmitter housing cover.
3. Use a small screwdriver to slide switch to desired position.
4. Replace transmitter cover.
4.5 

Electrical considerations

 WARNING
Ensure all electrical installation is in accordance with national and local code requirements.
 WARNING
Electrical shock
Electrical shock can result in death or serious injury.
Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical
equipment.
Emerson.com
 WARNING
Fully engage cover to comply with explosion-proof requirementa.
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN P
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
Electrical Installation
February 2024
PASSWORD
PASSWORD ENABLE
CHANGE PASSWORD
BACK TO MENU
EXIT MENU