Section 5: Basic Configuration/Start-up
November 2014
13. Choose a pre-defined calculation method based on a tank shape that corresponds to the
14. Choose Measure and Learn to configure the thresholds. For more information on the
15. Restart the device.
110
actual tank.
A. Choose None if volume calculation is not desired.
B. Use Volume Offset if you do not want zero volume and zero level to match
(for example, if you want to include the product volume below the zero level).
The Strapping Table option is used if the actual tank does not match any of the available
options for pre-defined tanks or if a higher calculation accuracy is desired.
Calculation Method:
F
fieldbus parameter:
OUNDATION
ADV_CONFIG_TB_1300 > VOL_VOLUME_CALC_METHOD.
Diameter:
F
fieldbus parameter:
OUNDATION
ADV_CONFIG_TB_1300 > VOL_IDEAL_DIAMETER.
Tank Length:
F
fieldbus parameter:
OUNDATION
ADV_CONFIG_TB_1300 > VOL_IDEAL_LENGTH.
Volume Offset:
F
fieldbus parameter:
OUNDATION
ADV_CONFIG_TB_1300 > VOL_VOLUME_OFFSET.
See
"Volume configuration" on page 78
Measure and Learn function, see
for more information.
"Echo tuning" on page
Reference Manual
00809-0100-4026, Rev HA
83.
Basic Configuration/Start-up