Emerson Rosemount 5400 Series Reference Manual page 182

Superior performance two-wire non-contacting radar level transmitter
Hide thumbs Also See for Rosemount 5400 Series:
Table of Contents

Advertisement

Section 8: Safety Instrumented Systems (4-20 mA Only)
November 2014
The HART loop must be referenced to ground in one point located between the power supply
and the load resistor. Either the negative or the positive pole of the power supply can be ground
referenced, depending on the placement of the load resistor. See
Figure 8-1. Reference Ground when the Load Resistor is Inserted in the Negative Line
Single point loop
ground reference
Table 8-2. Minimum Input Voltage (U
Hazardous approval
Non-hazardous Installations and
intrinsically safe installations
Explosion-proof / flameproof
installations
170
Power supply
Load resistor
Rosemount 5400
Series transmitter
Transmitter
housing ground
) at Different Currents
i
Current
3.75 mA
21.75 mA
Minimum input voltage (U
16 Vdc
11 Vdc
20 Vdc
15.5 Vdc
Safety Instrumented Systems (4-20 mA Only)
Reference Manual
00809-0100-4026, Rev HA
Figure 8-1
as an example.
)
i

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 5402Rosemount 5401

Table of Contents