Diagnosis of ASIsafe F adapters for front plate mounting

Status display
The status of a module is indicated by LEDs with continuous or flashing light. This enables
diagnostics at a glance:
● For AS-i communication via a dual LED
● For the switching state of the inputs with yellow LEDs
The following chapters provide an overview of the LED status displays of the AS-i modules.
Inputs
Each input has a yellow LED with designation "F-INx". For the functions, see the table below:
Table 11- 1
Diagnostics of the inputs via LED
F-IN x
Yellow
OFF
Status display AS-i / FAULT
All modules have a dual LED (green/red) for the "AS-i / FAULT" status display. For the
functions and remedies, see the table below:
Table 11- 2
Diagnostics of the AS-i status via LEDs
AS-i / FAULT
Possible cause
(green / red)
Green
Normal operation,
AS-i communication OK
Red
No AS-i communication:
Master is switched off or offline
Slave is not configured in the master
Incorrect slave type connected
Slave has the wrong address
Flashing
Module has slave address "0"
yellow/red
(delivery condition)
OFF
No AS-i voltage
AS-i voltage has been connected with reverse
polarity
AS-i voltage too low
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 08/2018, A5E03457306020A/RS-AK/010
Meaning
Signal activated
Signal deactivated
11.11 Diagnosis of ASIsafe F adapters for front plate mounting
Possible remedial measures
Ensure AS-i communication:
Switch on the master or switch it to online
mode
Reconfigure the master
Connect the correct module
Check/correct the slave address
Assign an address other than "0"
Switch on AS-i voltage
Connect it correctly
Measure the AS-i voltage (approx. 30 V DC)
AS-Interface 3SU14