Elements On The Front Plate - Siemens IM 328–N Description

Sinumerik 805sm/840c link to sinec l2–dp
Table of Contents

Advertisement

07.96
2.1.2

Elements on the front plate

Station address
The rotary switch is used to set the units place (first switch from top) and the
tens place (second switch from top) of the station address.
The hundreds place of the station address depends on the setting of the toggle
switch (upper position = 1 x 100, lower position = 0 x 100). Valid station ad-
dresses are between 3 and 124.
Note
Status display of
The status display (FAULT and RUN LED) can indicate the following states
the slave (LEDs)
of the SINEC L2-DP slave module.
(green LED)
Interface for slave
Via the interface X111 (SUB–D, socket, 9–way), the slave is connected to the
SINEC L2–DP field bus.
Note
To connect up to the SINEC L2–DP field bus, the bus connectors with the
following order numbers are required:
6ES5 762–2AA12
6ES5 762–2AA21
For information about the bus cable and the bus connector see:
Reference:
Siemens AG 1996 All Rights Reserved
SINUMERIK 805SM / 840C (BS)
2.1 Hardware of the module 6FC5 012–0CA03–0AA0
The software limits the station address to the range from 3 to 124.
A change in station address does not become active until after a restart of
the control.
RUN
FAULT
(red LED)
off
on
The module is being initialized
(this state lasts for a short period of time only)
on
off
Normal operating state, slave in cyclic operation
other states
Fault
(for L2–DP, DP standard, see Section 3.2.5)
(for L2–DP to V3.x see Section 3.3.5)
Order number
SINEC L2 bus connector (degree of protection IP 20, without
heavy–duty thread socket)
SINEC L2 bus connector (degree of protection IP 20, with
heavy–duty thread socket)
/1/, ET 200 Distributed I/O System Manual
6ZB5 430–0BH02–1AA0
Description
Remark
Designation
2
2-7