12.2 Electronic modules for ID key-operated switches
Diagnostics and messages
Individually codable ID key cannot be
deleted:
invalid key
Individually codable ID key cannot be
deleted:
Key to be deleted is not in the key list
The table below indicates how the manufacturer-specific diagnostics are reported:
Table 12- 8
Diagnostics and messages
Diagnostics and messages
Short-circuit
Self-test error / internal error
Individually codable ID key cannot be saved:
Key list is full
Individually codable ID key cannot be saved:
invalid key
Individually codable ID key cannot be deleted:
invalid key
Individually codable ID key cannot be deleted:
Key to be deleted is not in the key list
The manufacturer-specific diagnostic events listed in the table are reported to the IO-Link
1)
master via the diagnostics mechanism of IO-Link.
With the "process image input" (see Chapter "Process image (Page 334)"), you can
2)
determine via the group error (GE) bit or general warning (GW) bit in the user program
whether detailed information on diagnostics or messages is available in diagnostic data set
92. If bit (= 1) is set, you can obtain detailed information on what caused a "group error" by
reading data set 92.
GE = Group error: You can find detailed information in diagnostics data set 92 (see
3)
Chapter "Data set (index) 92 - diagnostics (Page 583)").
x: Bit set
—: Status does not change.
336
Possible cause
No valid individually codable ID key
inserted.
The inserted individually codable ID key
is defective.
The inserted individually codable ID key
was not previously assigned an
authorization level.
The manually entered identification
number in data set 80 has not been
assigned an authorization level
IO-Link for
event code
1)
0x7710
Possible remedial measures
Use an individually codable
ID key (white).
Check that the ID key has been
inserted as far as it will go.
Delete the corresponding ID key
by manually entering the
identification number in data
set 80.
Assign an authorization level to
the ID key.
Check the manually entered
identification number of the ID key
in data set 80.
PII
Data set 92
2)
SF
3)
X
X
X
X
X
X
X
X
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 08/2018, A5E03457306020A/RS-AK/010
LED
DEVICE
Red