Output Functions - Siemens SIRIUS ACT 3SU1 System Manual

Industrial controls, command and signaling devices pushbuttons and signaling devices
Table of Contents

Advertisement

IO-Link 3SU14
12.3 Electronic modules for IO-Link
12.3.2.2

Output functions

Static output
Description
In this mode, a value for the relevant output can be set and transferred from the IO-Link
master to the device. The value for the output is set by means of the output process data.
The output voltage corresponds to EN 61131-2.
Parameters
● Inverting output
PWM output
Description
The value of the output process data is read in this mode. The relevant output can be set as
a PWM output in this mode. PWM is activated by means of the output process data.
Parameters
● PWM frequency
● PWM duty cycle
● Inverting output
If "Inverting output" is deactivated, PWM is active at the output for as long as the
corresponding output process data bit is activated. If the relevant process data bit is
deactivated, the output is OFF.
If "Inverting output" is activated, PWM is active at the output for as long as the
corresponding output process data bit is deactivated. If the relevant process data bit is
activated, the output is OFF.
346
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 08/2018, A5E03457306020A/RS-AK/010