Diagnosis Of As-Interface Modules For Base Mounting - Siemens SIRIUS ACT 3SU1 System Manual

Industrial controls, command and signaling devices pushbuttons and signaling devices
Table of Contents

Advertisement

AS-Interface 3SU14

11.12 Diagnosis of AS-Interface modules for base mounting

11.12
Diagnosis of AS-Interface modules for base mounting
Status display
The status of a module is indicated by LEDs with continuous or flashing light. This enables
diagnostics at a glance:
● For AS-i communication via a red and green LED.
The following chapters provide an overview of the LED status displays of the AS-i modules.
Status display AS-i / FAULT
All modules have green and red LEDs for the "AS-i / FAULT" status display. For the
functions and remedies, see the table below:
Table 11- 3
Diagnostics of the AS-i status via LEDs
AS-i / FAULT
Possible cause
(green / red)
Green
Normal operation,
AS-i communication OK
Green
No AS-i communication:
Red
Master is switched off or offline
Slave is not configured in the master
Incorrect slave type connected
Slave has the wrong address
Flashing green
Module has slave address "0"
Red
(delivery condition)
Flashing
Overload of the outputs
alternately
green/red
1
OFF
No AS-i voltage
AS-i voltage has been connected with reverse
polarity
AS-i voltage too low
Only 4DI/4DO and 4DI/3DOAB modules
1
294
Possible remedial measures
Ensure AS-i communication:
Switch on the master or switch it to online
mode
Reconfigure the master
Connect the correct module
Check/correct the slave address
Assign an address other than "0"
Disconnect actuator cables
Check actuators and cables
Switch on AS-i voltage
Connect it correctly
Measure the AS-i voltage (approx. 24 V DC or
30 V DC)
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 08/2018, A5E03457306020A/RS-AK/010