MC Protocol Communication Function
9.4.2 Example of Bulk Write
Form of bulk write command in bit unit (binary) and Example of writing 8 points
from internal relay M100 to M107 (device numbers of FP7: R64 to R6B)
Command
Form
Command
Subcommand
Starting device
Device code
No. of devices
Data of specified device
The maximum number of bits that can be written at once is 7168.
9-14
Example
L
0x01
0x0401 Bulk write
H
0x14
L
0x01
0x0001 Bit unit
H
0x00
L
0x64
0x00
H
0x00
0x90
Device M
L
0x08
H
0x00
0x00
M100 off
0x10
M102 on
0x01
M104 off
0x11
M106 on
M101 off
M103 off
M105 on
M107 on