7.2.2 CONSET

• Makes the connection setting parameters specified by [S1] and [S2] to the connection in the
range specified by [D1] and [D2].
• CY (SR9) and SD29 are cleared to 0 when this instruction is executed.
(They are set when an incorrect IP address is specified or IP address is not established.)
• Check if "X62: IP address established" is ON before executing the instruction.
 Instruction format
R0
X62
CONSET
 Operation unit (i)
• There is no operation unit.
 List of operands
Operand
Description
Specify the starting address storing the operation setting parameter or a character constant.
S1
Specify the starting address storing the port setting parameter or a character constant.
S2
Specify the device address storing a setting start connection number or a constant.
D1
Specify the device address storing a setting end connection number or a constant.
D2
 Available devices (●: Available)
16-bit device
Operand
WX
WY
WR
S1
S2
D1
D2
 Processing
• Makes the connection setting parameters specified by [S1] and [S2] to the connection in the
range specified by [D1] and [D2].
• When an incorrect IP address is specified, an error is set to CY flag and it becomes no
operation.
• It can be executed when X62: IP address established is ON. If it is OFF when executing the
instruction, an error is set to CY flag and it becomes no operation.
7-8
"GP,OPTNAV,SV,AUTO,UDP"
S1
WL
WS
SD
DT
LD
UM
"PORT=9000,DISCONT=0"
S2
32-bit
Integer
device
TS
TE
WI
WO
IX
K
CS
CE
U1
U16
D1
D2
Real
num-
String
ber
U
H
SF
DF
" "
Index
modifier

Advertisement

Table of Contents
loading

Table of Contents