 Operand [S1] setting
• Specify the device address storing the text creation form or character constant (max. 256
characters).
• The text creation form is composed of a main text, conversion form (such as %d, %e),
linefeed code (\n) and tab code (\t).
• Up to 4096 characters can be specified for the text creation form. An operation error occurs
when it exceeds 4096 characters.
• Up to 16 digits can be specified for one conversion form. An operation error occurs when it
exceeds 16 digits.
• The maximum number of characters after conversion for a single datum execluding %s is 32.
An operation error occurs when it exceeds 32 characters.
• The maximum number of characters after conversion of %s is 4096.
• All strings that are not recognized as conversion forms are treated as main texts.
Example) Conversion form which does not allow capital letters (such as %D, %S)
Characters which are not recognized as judgement characters of conversion forms
are included (such as %A, %Z)
Explanation of text creation form
"\tFloor A: %d°C\n"
In the area where the conversion form is described, the output data specified by S2 is
stored according to the conversion form
* For information on the conversion form, refer to the table of conversion form.
* Linefeed code (\n) is converted to CRLF (0A0Dh).
* Tab code (\t) is converted to HT (09h).
Linefeed code
Conversion form
Body
Tab code
6.3 How to Use Event Mail Transmission
* When entering '%' in body
%: %%