MC Protocol Communication Function
9.2 How to Use MC Protocol Communication
9.2.1 Setting with Tool Software
Use the programming tool software "FPWIN GR7" to make the settings.
PROCEDURE
1. Select "Options" > "FP7 Configuration" > "Built-in ET-LAN" in the menu bar.
The Built-in ET-LAN setting dialog box opens.
2. Select any "User connection information setting" in the left pane.
3. Change the setting of "Connection to use specification" to "Use".
4. Select "MC protocol (QnA compatible 3E frame, binary) from the list of
"Operating mode setting".
5. Set "Communication type", "Open type (server/client)", "Open type
(automatic/manual)" and "Home port number".
6. Press the [OK] button.
KEY POINTS
•
For using multiple connections, set port numbers so that they are not
overlapped.
•
For the MC protocol communication, the setting for "MEWTOCOL
communication type" is not required.
9-4